148 EtherNet/IP – Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 0h (0 decimal) –> READY.
•
Enter 1h (1 decimal) –> ENABLED (Running forward).
•
Enter 2h (2 decimal) –> ENABLED (Running reverse).
51.27 FBA A par refresh
1
= Refresh
Validates the FENA-11/-21
configuration parameter settings.
20.01 Ext1 commands
12
= Fieldbus A
Selects the fieldbus A interface as
the source of the start and stop
commands for external control
location 1.
22.11 Speed ref1 source
4
=
FB A ref1
Selects the fieldbus A reference 1
as the source for speed reference
1.
1)
Read-only or automatically detected/set
2)
Example
Drive parameter
Setting for ACS880
/ACS580 drives
Description