22 Introduction to the manual
Protocols
The FENA adapter module is compatible with Ethernet standards
IEEE 802.3 and IEEE 802.3u.
This table shows the protocols supported by the FENA adapter
module from SW version 0.290 onwards.
This table specifies the clients/masters that are compatible with the
supported protocols.
Modbus/TCP
1)
EtherNet/IP™
PROFINET IO
FENA-01
x
x
x
FENA-11
x
x
x
FENA-21
x
x
x
1)
In addition to Modbus/TCP, FENA-01/-11/-21 supports Modbus over
UDP.
Protocol
Compatible client/master
Modbus/TCP
1)
All Modbus/TCP clients that support:
• Modbus Application Protocol Specification v1.1b
• Modbus Messaging on TCP/IP Implementation Guide
v1.0b
EtherNet/IP
All EtherNet/IP clients that support:
• The CIP Networks Library, Volume 1, Common
Industrial Protocol (CIP), Edition 3.0 May, 2006
• The CIP Networks Library, Volume 2, EtherNet/IP
Adaptation of CIP, Edition 1.2 May, 2006
• Recommended Functionality for EtherNet/IP Devices
Version 1.2, Feb., 2006
PROFINET IO
All PROFINET IO masters that support:
• GSDML file version 2.20
• PROFINET IO protocol according IEC standards
61158 and 61784
• PROFINET-IO conformance class B
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...