284 PROFINET IO – Start-up
7. Define the process data transferred to and from the drive in
parameter groups 52 and 53.
Note:
The adapter module automatically sets the
communication profile-specific virtual address for the Status
word in parameter 52.01 and for the Control word in parameter
53.01.
8. Save the valid parameter values to permanent memory with
parameter 96.07 Parameter save manually.
9. Validate the settings made in parameter groups 51, 52 and 53
with parameter 51.27 FBA A par refresh.
10. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples – ACS880
Speed control using PROFIdrive communication
profile with PPO Type 4
This example shows how to configure a basic speed control
application that uses the PROFIdrive profile. In addition, some
application-specific data is added to the communication.
The start/stop commands and reference are according to the
PROFIdrive profile, speed control mode. For more information, see
the PROFIdrive state machine on page
312
.
The reference value ±16384 (4000h) corresponds to parameter
46.01 Speed scaling in the forward and reverse directions.
Direction
PZD1
PZD2
PZD3
PZD4
PZD5
PZD6
Out
Control
word
Speed
reference
Constant speed 1
1)
Constant speed 2
1)
In
Status
word
Speed actual
value
Power
1)
DC bus voltage
1)
1)
Example
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...