110 Modbus/TCP – Diagnostics
Internal error code registers
A Modbus query can fail in many ways in the drive. The Modbus
standard does not specify detailed error descriptions. In addition to
the standard error codes, the FENA adapter module provides an
internal error register area for more detailed diagnostics.
The internal error register area is used if Modbus error code 0x04
occurs. The registers contain information about the last query. You
can figure out the reason of the failure by reading the registers.
The internal error register is cleared when a query has finished
successfully.
Address
Registers (16-bit word)
(4)00090
Reset internal error registers (0 = Do nothing, 1 = Reset)
(4)00091
Function code of the failed query
(4)00092
Internal error code; see the error number.
(4)00093
Failed register
(4)00094
Last register that was written successfully
(4)00095
Last register that was read successfully
Error code
Description
Situation
0x00
No error
Used when a Modbus query was
successful
0x02
Low or high limit
exceeded
Change access with a value
outside the value limits
0x03
Faulty subindex
Access to an unavailable
subindex of an array parameter
0x05
Incorrect data type
Change access with a value that
does not match the data type of
the parameter
0x65
General error in drive
communication
Undefined error when handling a
Modbus query
0x66
Timeout
Timeout in drive communication
when handling a Modbus query
0x70
Read-only
An attempt to write a non-zero
value to a read-only drive
parameter
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...