PROFINET IO – Communication protocol 339
Parameter data transfer examples
The following examples show how parameter data is transferred
using the DP-V1 mechanisms READ and WRITE.
Note:
Only the data block part of the request is presented in the
examples. See section
Read and write blocks
on page
331
.
Example 1a: Reading a drive parameter (array
element)
Drive parameters are addressed so that the drive parameter group
corresponds to the
Parameter index
(PNU), and the drive
parameter number within the group corresponds to the
Subindex
(IND). In the following example, a value is read from drive
parameter 12.04 (0C.04h).
•
DP-V1 Write request (Read parameter value):
DP
header
01 01 B0 2F 0A 05 01 01 01 10 01 00 0C 00 04
DP trailer
DP-V1 Command
PROFIdrive V3 Parameter Channel
Slot number
Subslot number
Index
Data length
Request reference
Request ID (01h= Request Parameter
Drive object ID
Number of parameters
Attribute (10h = Value)
Number of elements
Parameter index
Subindex
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...