PROFINET IO – Start-up 249
FENA-01/-11/-21 configuration parameters – group A (group 1)
Note:
The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
•
parameter group 51 in ACS355, ACSM1, ACS850 and
ACQ810
•
parameter group 51 in ACS880 and ACS580 if the adapter is
installed as fieldbus adapter A or group 54 if the adapter is
installed as fieldbus adapter B.
No.
Name/Value
Description
Default
01
FBA TYPE
Read-only.
Shows the fieldbus adapter type
as detected by the drive. The value cannot be
adjusted by the user.
If the value is
0
= None, the communication
between the drive and the module has not
been established.
128
=
ETHER-
NET
02
PROTOCOL/
PROFILE
Selects the application protocol and
communication profile for the network
connection.
The selections available for PROFINET IO
communication are listed below.
1)
0
= Modbus/TCP: ABB Drives profile -
Classic
0
1)
ACS355:
FB PAR 2
ACSM1:
FBA PAR2
ACS850/ACQ810:
FBA par2
ACS880/ACS580:
Protocol/Profile
10
= PNIO Pdrive
PROFINET IO protocol: PROFIdrive profile
11
= PNIO ABB Pro PROFINET IO protocol: ABB Drives profile
12
= PNIO T16
PROFINET IO protocol: Transparent 16-bit
profile
13
= PNIO T32
PROFINET IO protocol: Transparent 32-bit
profile
14
= PNIO PdriveM
PROFINET IO protocol: PROFIdrive
positioning mode
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...