EtherNet/IP – Communication profiles 175
Status word contents
The table below shows the contents of the Status word for the ABB
Drives communication profile. The upper case boldface text refers
to the states shown in the state machine on page
177
.
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
RDY_RUN
1
READY TO OPERATE
0
OFF1 ACTIVE
2
RDY_REF
1
OPERATION ENABLED
0
OPERATION INHIBITED
3
TRIPPED
1
FAULT
0
No fault
4
OFF_2_STA
1
OFF2 inactive
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 inactive
0
OFF3 ACTIVE
6
SWC_ON_
INHIB
1
SWITCH-ON INHIBITED
0
–
7
ALARM
1
Warning/Alarm
0
No warning/alarm
8
AT_
SETPOINT
1
OPERATION.
Actual value equals reference
(= is within tolerance limits, ie, in speed
control, speed error is 10% max. of nominal
motor speed).
0
Actual value differs from reference (= is
outside tolerance limits).
9
REMOTE
1
Drive control location: REMOTE (EXT1 or
EXT2)
0
Drive control location: LOCAL
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...