72 Modbus/TCP – Start-up
Starting up fieldbus communication for ACS850
and ACQ810 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive with parameter 50.01 FBA enable.
3. With parameter 50.02 Comm loss func, select how the drive
reacts to a fieldbus communication break.
Notes:
•
This function monitors both communication between the
fieldbus master and the adapter module and
communication between the adapter module and the drive.
•
In ACQ810, you can select the control locations to be
monitored with parameter 50.21 Comm loss enable. By
default, the monitoring is enabled in both control locations
(EXT1 and EXT2).
4. With parameter 50.03 Comm loss t out, define the time
between communication break detection and the selected
action.
5. Select application-specific values for parameters
50.04…50.11.
Examples of appropriate values are shown in the tables below.
6. Set the module configuration parameters in group 51.
•
Select the communication protocol and profile with
parameter 51.02 and configure the network settings with
parameters 51.03…51.13.
•
With parameters 51.20 and 51.21, select how the adapter
module detects fieldbus communication breaks.
Summary of Contents for FENA-01
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 32: ...32 Introduction to the manual ...
Page 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Page 42: ...42 Mechanical installation ...
Page 46: ...46 Electrical installation ...
Page 48: ......
Page 94: ...94 Modbus TCP Communication profiles ...
Page 106: ...106 Modbus TCP Communication protocol ...
Page 112: ...112 Modbus TCP Diagnostics ...
Page 114: ......
Page 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Page 180: ...180 EtherNet IP Communication profiles ...
Page 246: ......
Page 304: ...304 PROFINET IO Start up ...
Page 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...