6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 877 -
commences to operate the devices. Table 4.11-5 shows start commands.
2
Note: If a stop command is applied to the ASEQ01 function, the operation of the control
logic will be canceled promptly provided that the control logic is not operating the
device. Alternatively, the control logic can wait for the operation being completed,
if the control logic is able to determine to continue the operation. Table 4.11-4
shows the stop commands.
3
Note: See section 4.11.5. Table 4.11-9 and Table 4.11-10 show the emergency commands.
4
Note: After the reception of the start command, the execution state can be monitored.
Table 4.11-7 shows the execution states.
5
Note: The stop signal is provided for the logic. Table 4.11-6 shows the results of the stop
signals.
6
Note: Following the generation of a control command by the control logic, if the control
command fails to initiate the operation of a device, the control logic determines
that the control command has failed. The control logic will generate signals in
order to express “Control failure”.
When a stop command is generated during the selection of Device #3, the control logic
will clear the operation if the control logic can determine that the operation of Device #3 is
complete. Figure 4.11-3 shows that Device #3 unable to operate following reception of the stop
command.
*
3
The operating state turns to OFF, when the operation of Device#3 finishes
following the reception of a stop command from the ASEQ01 function.
Operating state
Selection signal for Device #2
Selection signal for Device #3
Selection signal for Device #1
Control logic in service.
Completion of closing
Start to close
Completion of closing
Start to close
ON
OFF
*
1
The ASEQ01 function generates a select signal for stopping the control logic.
*
2
The ASEQ01 function generates an operate signal for stopping the control logic.
*
4
The operation of Device#3 failed.
Figure 4.11-3 Timing chart for an automatic sequence when a stop command is injected during
the operation of Device#3
Figure 4.11-4 depicts the operating sequence when an emergency command is input; the
control logic will cancel the operation in accordance with the execution state given from a
device. If the operation signal is not controlling the device, the control logic will clear the
operation promptly. If the operation signal is controlling the device, the control logic will clear
the operation when the control logic function can determine that the operation of the device is
complete, in this case Device#1.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......