6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 956 -
Power supply module (PWS)
5.5.1
PWS structure
The power supply module (PWS) consists of a DC/DC converter and line noise filters.
There are two types for the PWS module about the DC rated voltage. The first type is for “110-
250 Vdc” rated, and the second is for “24-60Vdc” rated. One of DC rated voltage types is chosen
with the ordering table, and then the type is applicable in the PWS.
Table 5.5-1 PWS specifications
DC rated
voltage
5
Voltage fluctuation
permissible
Description
110-250 Vdc
88-300 Vdc
Input voltage (110/125Vdc, 220/250Vdc) is
available where the voltage varies in ±20% of the
rated voltage (110V× 80% to 250V×120%).
24-60 Vdc
19.2-72 Vdc
Input voltage (24/48/60Vdc) is available where the
voltage varies in ±20% of the rated voltage (24V×
80% to 60V×120%).
Note: The IED composed of a PWS module whose DC rated voltage is “110-250 Vdc”, can
run on AC power supply (100–220Vac).
However, it is recommended to input AC power only for temporary operations such
as tests where DC power cannot be inputted. In addition, if the supervision function
is enabled, the IED detects the Power failure (error) when AC power is inputted.
Figure 5.5-1 shows the difference between ‘Compression plug type terminal’ and ‘Ring type
terminal’. Alpha-numeric reference “T*” identifies slot locations, and an asterisk “*” shows its
slot number. An external connection figure illustrates the PSW location (see
Appendix: Typical
External connection
).
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......