6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 432 -
Wait for a command
Do nothing
Receiving
“Cancel command”
Discarding of
“select command”
Cancel logic
“Remote-cancel”
Cancel logic
“Local-cancel”
Return to
“Wait
for a command
”
Failed
Success
F/S
When Cancel is issued
from the remote-end
When Cancel is issued
from the local-end
Figure 3.1-3 Scheme “Cancel command”
Reception of “operate command”
Following successful completion of the “select command”, the control function is ready to
receive an “operate command” in order to control a device. The receipt of “operate command”
is divided into “Operate command ‘On’ (Closing)” and “Control command ‘Off’ (Open)”; each of
the two commands is carried out based upon its origin i.e. “Remote”, “Local”, and “PLC”. If the
“operate command” is completed, the “select command” can be released; then a new “Wait for
a command” stage can commence for receipt of a new “select command”.
Failed
Wait for a command
Release of
“select command”
Return to
“Wait
for a command
”
Receiving
“Operate command”
Operate logic
“Remote-On-control”
Operate logic
“Remote-OFF-control
”
Operate logic
“Local-On-control”
Operate logic
“Local-OFF-control”
Operate logic
“PLC-On-control”
Operate logic
“PLC-OFF-control”
Failed
Success
F/S
Receiving
“Select command”
Select logic
“Remote-OFF-control
”
Select logic
“Local-On-control”
Select logic
“Local-OFF-control”
Select logic
“PLC-On-control”
Select logic
“PLC-OFF-control”
Select logic
“Remote-On-control”
Figure 3.1-4 Scheme “Operate command”
(ii)
Command reception in DIR mode
In DIR mode, issuing an “operate command” is possible without the reception of the “select
command”. Thus, the reception of an “operation command” only features in the control scheme†.
We shall see the DIR mode later.
†Note: We can encompass the operation of the “select command” being performed
internally in the control scheme. Thus, the user is not required to take account of
the reception of the “select command”.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......