6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 583 -
Signal Number
Signal Name
Description
M/O
511001 800202EE65
DPSY02IN_TMP_40
DPSY02 user additional condition(PLC#1)
O
511001 810201EE66
DPSY01IN_TMP_41
DPSY01 user configurable operate condition(PLC#2)
O
511001 810202EE66
DPSY02IN_TMP_41
DPSY02 user configurable operate condition(PLC#2)
O
511001 820201ED50
DPSY01IN_TMP_28
DPSY01 control hierarchy condition(PLC#3)
M
511001 820202ED50
DPSY02IN_TMP_28
DPSY02 control hierarchy condition(PLC#3)
M
Table 4.2-19 PLC monitoring points (Output signal for BIO)
Signal Number
Signal Name
Description
511001 8202011DD3
DPSY01_OEX_BO
DPSY01 operate (CLOSE) command for Binary Output.
511001 8202021DD3
DPSY02_OEX_BO
DPSY02 operate (CLOSE) command for Binary Output.
511001 8102011DD0
DPSY01_FEX_BO
DPSY01 operate (OPEN) command for Binary Output.
511001 8102021DD0
DPSY02_FEX_BO
DPSY02 operate (OPEN) command for Binary Output.
Table 4.2-20 PLC monitoring points (Signals within operate logic)
Signal Number
Signal Name
Description
511001 8002011E7F
DPSY01_OEC_OK_CSF
DPSY01 Close direction execute command
511001 8002021E7F
DPSY02_OEC_OK_CSF
DPSY02 Close direction execute command
511001 8102011E82
DPSY01_OEC_OK_CS
DPSY01 Close direction execute command
511001 8102021E82
DPSY02_OEC_OK_CS
DPSY02 Close direction execute command
511001 8002011E7E
DPSY01_FEC_OK_CSF
DPSY01 Open direction execute command
511001 8002021E7E
DPSY02_FEC_OK_CSF
DPSY02 Open direction execute command
511001 8002011E7E
DPSY01_FEC_OK_CS
DPSY01 Open direction execute command
511001 8002021E7E
DPSY02_FEC_OK_CS
DPSY02 Open direction execute command
Table 4.2-21 PLC monitoring points (Output signal for response)
Signal Number
Signal Name
Description
511001 8002011E93
DPSY01_EX_CMP
DPSY01 completed control
511001 8002021E93
DPSY02_EX_CMP
DPSY02 completed control
511001 8602011E91
DPSY01_EX_FFL
DPSY01 failed control
511001 8602021E91
DPSY02_EX_FFL
DPSY02 failed control
(ix)
Setting names
Note: The “xx” of “DPSYxx” represents the DPSY function number. (e.g., if the DPSY01
is considered, the “xx” is equal to “01”. The suffix “xx” can be represented by either
a “01” or “02”.)
Table 4.2-22 Setting of Operate in DPSYxx
Setting Name
Description
Default
Setting item or value
DPSYxx-PLSM
Method of command output (DPSY01-02)
Fix
Fix/Var
DPSYxx-CPW
Duration of command output (DPSY01-02)
1.0[sec]
0.1~50.0[sec]
DPSYxx-RST
Detection time for terminating control (DPSY01-02)
30.0[sec]
0.1~100.0[sec]
DPSYxx-LGCTRCON
Logic selector for operate condition (DPSY01 -02)
Fixedlogic
Fixedlogic/PLC
DPSYxx-LGCFEXOT
Logic selector for command output (DPSY01 -02)
Fixedlogic
Fixedlogic/PLC
DPSYxx-CTREN
Activate control function (DPSY01 -02)
Close
Open / Close
DPSYxx-LGEXFFCT
Logic selector for operate condition (DPSY01 -02)
Fixedlogic
Fixedlogic / PLC
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......