6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1236 -
Oct.
Item
Value
Remarks
4
Start
68H
5
Control field
08H+ACD+
DFC
6
Address
1-254
Setting from the relay
7
Type identification (Type ID)
1
Customized by GR-TIEMS
8
Variable structure qualifier
81H
9
Cause of transmission (COT)
20/21
Customized by GR-TIEMS
10
Common address of ASDU
1-254
Linked with Address setting
11
Function type (FUN)
0-255
Customized by GR-TIEMS
12
Information number (INF)
0-255
Customized by GR-TIEMS.
Answer back of receiving
command INF
13
Double point information (DPI)
1/2
Answer back of receiving
command DCO
14
Millisecond (low)
0-59999
15
Millisecond (high)
16
M Invalid flag (MSB)
0-59+80H
17
Hours + Summer time flag (MSB)
0-23+80H
18
Supplementary information (SIN)
0-255
Answer back of receiving
command RII
19
Checksum
20
End
16H
Any comment with maximum 16 characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
Type ID
Type ID=20 (General command) is fixed.
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-12 and the
appendix†.
Table 11.4-12
INF category of Monitor direction
INF
Category
0 to 15
system functions
16 to 31
status
32 to 239
not used
240 to 255 generic functions
†Note: For more information, see
Appendix: IEC 60870-5-103 interoperability.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......