6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 938 -
signal monitoring points of the binary output circuits. The user can monitor the operations of
the binary output circuit using element ID together with function ID. When we assume that a
BO1A module is at IO#2 slot in the IED case, and if the user wishes to monitor the first-circuit
in the BO1A module, the user can see the operation using the element ID (8002001112) and
the function ID† of IO#2 slot.
†Note: A function ID identifies every IO slots. For example, with regard to the function
ID and the Data ID at IO#1 slot, see section 5.4.9(i). On the other hand, for IO#2
slot see section 5.4.9(ii).
(i)
CPL switch
When the user needs to operate the CPL for binary output circuit #1, the user should set
On
for the scheme switch [
BO1_CPL
]. Conversely, the user should set
Off
for the scheme switch
[
BO1_CPL
] if CPL is not required. Since all binary output circuits have CPLs setting between
On
and
Off
is required for every binary output circuit. The number of CPL is equal to the
number of binary output circuits: that is, if the BO1A module is selected, the number of CPLs
is 18. Note that the subsequent PLC settings described later require that
Off
be set for the
scheme switch.
(ii)
Selection of input signals
Since a binary input circuit is operated by commands introduced from other functions, eight
ports for input signals are provided, designated as
input-signal1
to
input-signal8
. The user
must ensure that
input-signal1
to
input-signal8
are configured with eight DataIDs. That is,
the user can select input-signals that are available from other functions, these input-signals
are designated using DataIDs. The user can key the DataIDs into settings [
Input signal1
] to
[
Input signal8
]. The DataIDs are selected from the
Signal monitoring point
list, which is
provided for every function.
(iii)
Logic gate switch
A binary input circuit has a logic scheme for the eight input signals, and can combine the eight
input signals as required using scheme switch [
LOGIC-SW
] for which the user should set either
AND
,
OR
or
XOR
.
(iv)
Delayed pick-up/delayed drop-off signal
An on-delay timer and an off-delay timer are provided in the CPL; both are used to adjust the
timing for binary output circuits, the user should set their respective time values for settings
[
On Delay Timer
] and [
Off Delay Timer
].
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......