of group settings (e.g., the ‘SYS_CHG’ signal; which has been connected with the trigger#9
using the setting [
Trigger ID9
], as default; we have been discussed in Chapter
Technical
description: Group setting for protection functions
.)
8.2.3
Screen information
Figure 8.2-5 illustrates the structure about the ‘Event Recored1’ group, which can be shown
the latest event#1 at the top structure (line
○
b
). The lines
○
c
and
○
d
describes how an event
occurred for the event#1. Preceding event#2, event#3, etc. are shown below the event#1.
Similarly, the information about the ‘Event Record2’ and ‘Event Record3’ groups are displayed
on the IED screen.
†Note: For more information about the screen operation, see Chapter
User interface:
Record sub-menu.
Event Record1
10:48 1/4
#1 2012-07-26
12:34:51.223
F.Record clear
On
#2 2012-07-25
10:56:12.021
Set group change
4
#3 2012-07-25
10:31:12.159
F.Record clear
On
#4 2012-07-23
23:56:12.159
○
a Event record1 list
○
b The latest event#1
○
c Trigger inform ation
○
d Trigger m ode inform ation
Screen scroll down
Detail inform ation about evolving faults
○
e Event#2
○
f Event#3
○
g Event#4
○
d Trigger m ode inform ation
Figure 8.2-5 Event information grouped in the Event record1
8.2.4
Setup for the event recorder
Consider that a trip-command, which is denoted with Data ID ‘4A1001 8300001B6F’, should
be sorted into the ‘Event record1’ group. The settings [
End of E.Record-1
]=256 and [
End of
E.Record-2
]=512 have been made as default; hence, we may select it with the trigger#157 by
setting the [
Trigger ID157
]= ‘4A1001 8300001B6F’. Set
On-OFF
for the [
Trigger Mode157
],
because the pulse-train of the trip command should be recorded along the pick-up and drop-off
times. Remember that the preferred name for the Trigger ID157 should be set using the [
Event
Name157
].
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......