6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1232 -
Oct.
Item
Value
Remarks
11
Function type (FUN)
0-255
Customized by GR-TIEMS
12
Information number (INF)
0-255
Customized by GR-TIEMS
13
Short-circuit location (SCL)
Customized by GR-TIEMS
17
Relative time (RET)
0-65535
Trigger condition to calculate RET is
customized by GR-TIEMS.
19
Fault number (FAN)
0-65535
Trigger condition of FAN increment is
customized by GR-TIEMS.
21
Millisecond
0-59999
23
M Invalid flag (MSB)
0-59+80H
24
Hours + Summer time flag (MSB)
0-23+80H
25
Checksum
26
End
16H
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
Signal name / signal description
The Data ID† (Sig. No.) showing the trigger of the frame is set from the signal list. If the
setting value (signal No.) is “0”, all setting items related the “Time-tagged measurand” are
disable and the frame is not provided.
The frame cannot be set to the object of GI and cannot be transmitted even though the
status of set signal changes from ON to OFF. If the metering values at the newest fault
record are transmitted as the status change frame, select the Data ID of “F.Record_DONE”
or “FAULT RECORD DONE” in the signal list of the relay.
†Note: A relevant Data ID is required to select in the signal list. The description of the
Data ID is obtained automatically on the setting.
Inverse
This setting is used to invert the logic of the signal assigned to the Data ID above. If the
frame is transmitted when the signal assigned to the Data ID is ON, leave the Inverse check
box blank. If the frame is transmitted when the signal is OFF, click the inverse check box
to be marked with “
”.
Type ID
Type ID=4 (Time-tagged measurand with Relative time) is fixed. In Type ID=4, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the fame
out of the standard is provided, the INF should be set referring Table 11.4-3 and the
Appendix†.
†Note: For more information, see
Appendix: IEC 60870-5-103 interoperability.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......