6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 874 -
4.11.1
Function setup
Figure 4.11-1 outlines the command reception in the ASEQ01 function. The ASEQ01 function
can generate a start command at the PLC monitoring point “ASEQ01_EXEC_START” (see
Table 4.11-5), when the start command is provided for the ‘ASEQ01_CONTROL_REQ’.
Similarly, when a stop command is received in the ASEQ01 function, the stop command will
be generated at the PLC monitoring point “ASEQ01_EXEC_STOP” (see Table 4.11-6) †.
†Note: Create “
IN1
” and “
IN2
”points in the user programming logic; make the connection
between the ASEQ01 function and the user programing logic. Refer to chapter
PLC function. The user-programming logic is also required to have output points.
For example, if the user wishes to control a CB using the logic, the logic should
have two output points for two binary output circuits (BOs). Figure 4.11-1 shows
how two BOs are used for CB closing and CB opening.
‡Note: The ASEQ01 function does not have the responsibility to restart the programmed
logic after an emergency stop signal has been applied. Therefore, the user should
program the logic to generate an operation result signal in case of the emergency
stop signal being applied in the logic. See section 4.11.5 for the emergency
operation.
‡Note: PLC connection point “ASEQ01_EXEC_RESET” is provided for stopping the
ASEQ01 operation, as shown in Table 4.11-4.
Device
ASEQ01_
EXEC_START
Driver
ASEQ01_
EXEC_STOP
OUT2
OUT1
ASEQ01
User programming logic for
CB control
logic
Binary Output
Circuit
4
Driver
Binary Output
circuit
4
Close
Open
In
Out
In
Out
IED
Remote operation
“Emergency stop”
“Reply Signal”
EMERSTOP_
EXEC_STOP
IED front panel
operation
IN1
Xxxxxx 8xxxxxxxxx
IN2
Xxxxxx 8xxxxxxxxx
ASEQ01-EXEC_RESET
‡
523001 800D01EDF2
ASEQ01_CONTROL_REQ
523001 700D016D08
EMERSTOP_CONTROL_REQ
523001 820D10ED50
Figure 4.11-1 ASEQ01 controls the user programing logic to operate a CB
Table 4.11-2 Mapping points for the r remote control commands
Signal Number
Signal Name
Description
M/O
523001 700D016D08
ASEQ01_CONTROL_REQ
ASEQ01 control command received. (Mapping Data)
M
523001 700D026D08
ASEQ02_CONTROL_REQ
ASEQ02 control command received. (Mapping Data)
M
523001 700D036D08
ASEQ03_CONTROL_REQ
ASEQ03 control command received. (Mapping Data)
M
…
…
…
523001 700D0F6D08
ASEQ15_CONTROL_REQ
ASEQ15 control command received. (Mapping Data)
M
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......