6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 754 -
Operate condition
User configurable operate condition (PLC#2 connection point)
Same Directional
Controlling Event
OFF
[SCDEN]*8
Fixedlogic
[
DPOS01-
LGEXFFCT
]
To selection logic
Additional condition (PLC#1 connection point)
DPOS01IN_TMP_38
512001 800301EE65
DPOS01IN_TMP_39
512001 810301EE66
Command
“ON-control” received
Command
“OFF control” received
received
&
&
&
&
&
1
≥
1
≥
DPOS01_3PH_STATE
DPOS01 function (Function ID: 512001)
Function
“Automatic sequence control” is in progress
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
Unmatched condition detected *5
Event suppression detected *6
= DPOS01_F_QLT_SPP
BI board connection error detected*7
= DPOS01_F_BI_ERR
(512001 8103011F5F)
(512001 8203011F60)
(512001 3103011001)
From Control hierarchy *9
From CMNCTRL
[
DPOS01-CTREN
]
On
DPOS01IN_TMP_28
512001 820301ED50
SERI_ERR
&
Serious error detection
From TRC
*
4
GEN.TRIP
General trip
From SOTFSW
*
1
CBK_STATE
Command blocking
*
1
Figure 4.8-31 Operate condition logic for On/Off in DPOS01
1
Note: “Command Blocking” disables all operation except for its own; “Command
Blocking” is implemented as “CBK” in a software switch controller (SOTFSW).
The IEC61850 standard defines “Command Blocking” as “CmdBlk”. For more
information on “CBK”, see Chapter
Control and monitoring application: Software
switch controller. See the signal ““CBK_STATE” in Table 4.8-6.
2
Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.8-6. For more information see Chapter
Control and
monitoring application:Common controls.
3
Note: Detection of event “device-travelling” signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the event is being detected. The detection signal is denoted
as “Travelling OR” in Table 4.8-6.
4
Note: If an IED in the process of issuing a trip command, all control operation is blocked
until the trip operation has been completed. If the IED has a relay application, the
trip command is issued at the output point “GEN.TRIP” in Table 4.8-6.
5
Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......