6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 521 -
‡Note: An “operate condition” is generated in the operate-condition logic( see Figure
Fixlogic
is set for scheme switch[
SPOS01-LGCTRCON
], If an
alternative “Operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative ”Operate-condition” can be connected to the above logic using
connection point #3 ”User configurable condition”. That is, set the scheme switch
[
SPOS01-LGCTRCON
] to
PLC
and use SPOS01IN_TMP_34.
‡‡
Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by [
SPOS01-RST
] has been reached.
§§Note: The signal “SPOS01_OEX-BO” is issued when
Fixlogic
is set for scheme switch
[
SPOS01-LGCFEXOT
]. The “Operate completed “signal can also be issued from
logic programmed by the user in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal “Operate completed”.
Hence, this signal is now generated by the user-programmed logic at connection
point # 2 “user-configurable condition”. That is, set the scheme switch [
SPOS01-
LGCFEXOT
] to
PLC
and use “SPOS01IN_TMP_42”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of the output signal. When
Var
is set for scheme switch
[
SPOS01-PLSM
], the output period of the signal is defined by the setting
[
SPOS01-CPW
]. When
Fix
is set, the signal ceases when the 43-switch is changed.
When
Latch
is set, the output signal is kept issuing until the reception of
“Command Off”.
††
Note: To identify the input and output signal-points of the other SPOS logics, see Table
4.1-14, Table 4.1-15, Table 4.1-19, and Table 4.1-20.
Output signal to BO
The SPOS01 function, in Figure 4.1-22, can issue an “Operate” signal at the output-point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the signal “Remote-Off-
Control” is true.
(iii)
Receiving “operate command On” from the local-end
Figure 4.1-23 depicts the reception of the operate command for ‘On’ from the local-end.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......