6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 592 -
Signal acquisition logic in DPSY01
“DPSY01_3PH_STATE”
(511001 3102011001)
To select and operate
condition logics
[
DPSY01-DEVTYPE
]
1-Pol
e
Open
Faulty
Intermediate
Close
Event
Suppression
detector
BI signal selected by
setting [
DPSY01A-NOPSG
]
[
DPSY01-EN
]
On
&
BI signal selected by
setting [
DPSY01A-NCLSG
]
N/O contact
signal
N/C contact
signal
Single phase signals
&
&
1
≥
&
&
&
&
DPSY01
Signals from the
devices
Output
‡
“DPSY01_
F_QLT_SPP
”
(511001 8102011F5F)
BI circuit and DPSY01
Figure 4.2-41 Acquisition of single-phase signal at DPSY01
‡Note: In Figure 4.2-41 two signals can be issued “DPSY01_3PH_STATE” and
“DPSY01_F_QLT_SPP”, which are the same as the signals in the Figure 4.2-40.
Event suppression
If the status of a device “chatters” for a short time, the DPSY function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPSY function;
hence, event suppression can be required to reduce the additional burden created.
1 3 5 7
Signal
from device
2 4 6 8
[
DPSY-TELD
]
[
DPSY-TELR
]
[
DPSY-NELD
]
Suppressed
signal
A
C
D
E
B
Time.................
Figure 4.2-42 Iterative signals and signals suppressed
Figure 4.2-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time ‘B’). This is because the function can count the iterative number of
incoming signals. Detection commences at Time ‘A’, the setting [
DPSY-NELD
] is provided so
that the suppression commences at Time B. The setting [
DPSY-TELD
] is pertains to the
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......