6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 442 -
3.4.2
PLC_BIT/UNIT/BOOL signal
The control and monitoring functions are mutually interconnected within the IED; hence,
cascading features are provided to transfer information between them so that the user does
not need to check the interconnections. Approximately 1500 signals are included to facilitate
the internal connection of the control and monitoring functions; their signals are distributed
into BIT, UNIT, BOOLEAN types, which are listed later. Figure 3.4-4 exemplifies the
“PLC_BIT_0201” signal, which may be used for recording events and other purposes.
CMNCTRL2
function
(5A0101 8002001F40)
PLC_BIT_0201
5A0101 800200EF40
PLC_O_BIT_0201
For
・
Event record function
・
Communication (required mapping)
・
LEDs
・
IED screen display
・
Binary output module
etc…
Information
cascaded
§
Figure 3.4-4 Cascading information using signal “PLC_BIT_0201”
3.4.3
Provision of selected status
Let us assume that a select-command is sent for an IED to control a target-device by the
substation automation system (SAS†), but the target-device is not ready to be controlled. The
unready condition might be due to the target-device already being in operation (e.g., CB
tripping) or a failure of the device may have occurred; thus, the IED has to drop the select-
command. If this occurs, the IED is required to send a message stating the reason to the SAS†.
Table 3.4-2 lists the messages generated in the CMNCTRL1 function describing the failure.
Table 3.4-2 Reason messages due to the release of the select-command
Signal Number
Signal Name
Description
5A0001 3008001FB4
SCS_CTLNUM
Reason codes for the SAS†
5A0001 2008001008
SCS_ORCAT
5A0001 2208001001
SCS_ADDCAUSE
5A0001 6A08001009
SCS_ORIDENT
5A0001 3008001FB4
SCS_CTLNUM
†Note: The user should recognize that the reason messages are only available for
operation with the GCS1000 control system manufactured by Toshiba.
3.4.4
Miscellaneous settings
The CMNCTRL1 function has the following five common settings:
1. Control direction:
The [
SDCEN
] can configure the control directions of the SPOS,
DPOS and TPOS functions. If required these functions can be in the
same control direction, set
On
for the scheme switch [
SDCEN
].
2. Return value:
When the number of the counter reaches its maximum value (in case
of the default setting, 999,999), it can return and begin
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......