6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 398 -
Collection: The signals, received from the various protection functions (shown as
‘FC18’ and others; see Table 2.26-2 and Table 2.26-6), are gathered in the Trip-signal
collection logic.
Generation: CB trip signal generation, Sub-signal generation for blocking ARC§, and
Alarm-signal generation logics are provided.
A binary output (BO†) circuit must be selected in order to energize the trip coil of the
CB#1 and CB#2. That is, the BOs should be made the connection with the CB#1 and CB#2 trip
coils; the drive signal should be outputted (i.e., ‘TRIP-COMMAND1-A,-B,-C’ and ‘TRIP-
COMMAND2-A,-B,-C’†). The Alarm-signal generation logic operates to provide a trigger signal
for the recording function‡.
†Note: The internal connection between the TRC function and the BIO module should be
performed using the BIO settings or the PLC programming. The user can program
the connection the PLC monitoring point ‘TRIP-COMMAND1-A (8000001B20) etc.’
with preferred BO circuits using the settings [
Input signal1
] etc. of each BO on the
BIO module. The externally wired connection between the BIO module and trip
coil circuit is made at the IED terminals. For more information with regard to the
BO circuit concerning the Element ID (Data ID), see Chapter
Technical
description: Binary IO module.
§Note: Autoreclose (ARC) and other protection functions are discussed separately. See
Chapter
Relay application, respectively.
‡Note: For information on recording, see
Chapter Recording function.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......