6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 906 -
5.2.3
Setting VCT ratio
As input sources are transformed with various VTs and CTs in the power system, the user shall
set each VT or CT ratio at each VCT terminal.
(i)
Setting a ratio for the VT
When the VT quantity applied at the VCT terminal, a ratio of the primary voltage to the
secondary voltage should be set. A voltage is applied at the first terminal (Ch1) at VC1 alpha-
numeric reference, the user should set the ratio for the setting [
AI1_Ch1_Ratio
]. For example,
the user is requires to set a value ‘3636’ for the [
AI1_Ch1_Ratio
] when the primary is 400kV
and the secondary is 110V (i.e., 400kV/110V=3636). The channel position on the VCT is
discussed in the preceding section
VCT
.
(ii)
Setting a ratio for the CT
When the CT quantity flows into the VCT terminal, a ratio of the primary current to the
secondary current should be set. For example, the user is required to set a value ‘4000’ for the
[
AI1_Ch1_Ratio
] when the primary is 4000A and the secondary is 1A (i.e., 4000/1=4000).
(iii)
Setting list
Setting of AC analog input(Function ID: 200201)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
VC1
AI1_Ch1_Ratio
1.000 to 20,000.000
–
For AC analog input ch#1 at VCT#1
1.000
alpha-numeric
AI1_Ch2_Ratio
1.000 to 20,000.000
–
For AC analog input ch#2 at VCT#1
1.000
reference
AI1_Ch3_Ratio
1.000 to 20,000.000
–
For AC analog input ch#3 at VCT#1
1.000
AI1_Ch4_Ratio
1.000 to 20,000.000
–
For AC analog input ch#4 at VCT#1
1.000
AI1_Ch5_Ratio
1.000 to 20,000.000
–
For AC analog input ch#5 at VCT#1
1.000
AI1_Ch6_Ratio
1.000 to 20,000.000
–
For AC analog input ch#6 at VCT#1
1.000
AI1_Ch7_Ratio
1.000 to 20,000.000
–
For AC analog input ch#7 at VCT#1
1.000
AI1_Ch8_Ratio
1.000 to 20,000.000
–
For AC analog input ch#8 at VCT#1
1.000
AI1_Ch9_Ratio
1.000 to 20,000.000
–
For AC analog input ch#9 at VCT#1
1.000
AI1_Ch10_Ratio
1.000 to 20,000.000
–
For AC analog input ch#10 at VCT#1
1.000
AI1_Ch11_Ratio
1.000 to 20,000.000
–
For AC analog input ch#11 at VCT#1
1.000
AI1_Ch12_Ratio
1.000 to 20,000.000
–
For AC analog input ch#12 at VCT#1
1.000
AI1_Ch13_Ratio
1.000 to 20,000.000
–
For AC analog input ch#13 at VCT#1
1.000
AI1_Ch14_Ratio
1.000 to 20,000.000
–
For AC analog input ch#14 at VCT#1
1.000
†Note: For more information, see Chapter
User interface: AC analog input.
‡Note: The number of AC analog input channels depends on the configuration of the VCT
type and the VCT slot. Thereby, the user has to set the value of the VCT ratio
corresponding to a specific auxiliary VT/CT.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......