6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 657 -
(ii)
Mapping output data
The user should group the OPTIM signals with regard to GOOSE and REPORT; the user
should map them for the IEC61850 communication using the GR-TIEMS. Figure 4.4-15 shows
how to map a signal; it shows that the signals of the OPTIM function are required to map for
the IEC61850 communication.
Table 4.4-5 Mapping signals for SPC object
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GGIO3302$SPCSO1$origin
orCat
orCategory
ST
529001 200C011008
OPTR01_ORCAT
Ctrl/GGIO3302$SPCSO1$origin
orIdent
Octet64
ST
529001 310C01170A
OPTR01_ORIDENT
Ctrl/GGIO3302$SPCSO1
stVal
BOOLEAN
ST
529001 310C011EA1
OPT_RST_CMD
Ctrl/GGIO3302$SPCSO1
Q
Quality
ST
301001 3110041005
Qual_Val
Ctrl/GGIO3302$SPCSO1
T
Timestamp
ST
200301 9010001006
SYS_TIME
Ctrl/GGIO3302$SPCSO1
stSeld
BOOLEAN
ST
529001 000C011D90
OPTR01_STSELD
Note:
“Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.4-15 orCat attribute mapped into SPCSO object of GGIO3302
(iii)
Mapping input data
The OPTIM function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “OPTR01_CONTROL_REQ”. Table 4.4-6 shows the input-point
“OPTR01_CONTROL_REQ” and the Object reference
“Ctrl/GGIO3302$SCPSO”; the user should
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......