6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 820 -
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK
† condition
S
R
0.1
– 50.0 s
[
TPOS01-CPW
]
Operate Cmd.
without ILK
† condition
Operate condition
‡
[
TPOS01-LGCTRCON
]
Fixedlogic
Fixedlogic
[
TPOS01-LGP2EXOT
]
DEV01_CONTROL_REQ
Command Local-P2-Control
”
513001
_
7004016D08
TPOS01IN_TMP_28
513001 810401EE57
User configurable condition (PLC#3 connection point)
“TPOS01_P2EC_OK_CSF”
(513001 8004011E7F)
&
&
1
≥
&
1
≥
1
≥
&
&
&
“TPOS01_P2EX_BO”
(513001 8204011DD3)
§§
Input
Output
Operate logic in TPOS01
To BO connection
“TPOS01_P2EC_OK_CS”
(513001 8304011E82)
[
TPOS01-PLSM
]
*
Fix
Var
Operate Failed
[
TPOS01-RST
]
ASEQ function
§
” is in progress
ASEQ_MULTI_SEL
“TPOS01_P2EC_OK_CSF”
(513001 8004011E7F)
“TPOS01_EX_FFL”
(513001 8604011E91)
‡‡
To
“Wait for a command”
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
≥
&
“TPOS01_EX_CMP”
(513001 8004011E93)
Operate Completed
1.0s- 100.0s
0
t
ILK
†
condition (“P2”) passed
TPOS1-P2
1
≥
ILK
†
bypassing
ICB_STATE
Figure 4.9-35 Operate ‘P2-control’ on the front panel in TPOS01
††
†Note: The ILK function can provide the operation criteria for “P2” control.
‡Note: An “operate condition” signal is generated in the operate-condition logic (Figure
Fixlogic
is set for scheme switch [
TPOS01-LGCTRCON
]. If an
alternative “operate-condition is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the to the above logic using
connection point #3 “User configurable condition” That is, set the [
TPOS01-
LGCTRCON
] to PLC and using “ TPOS01IN_TMP_28”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When
Var
is set for scheme switch
[
TPOS01-PLSM
], the output period of the signal is defined by the setting
[
TPOS01-CPW
]. When
Fix
is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [
TPOS01-RST
].
§§Note: The signal “TPOS01-PIEX-BO” is issued when
Fixlogic
is set for the [
TPOS01-
LGP1EXOT
]. The “Operate completed” signal can also be issued from the logic
programmed by the user in place of the logic shown in Figure 4.9-26 . The user-
programmed logic is connected internally to the signal “operate completed”, hence
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......