6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 852 -
Signal Number
Signal Name
Description
513001 8204021F59
TPOS02_QLT_SPP
Event suppression detected (TPOS02)
513001 8204031F59
TPOS03_QLT_SPP
Event suppression detected (TPOS03)
…
…
…
513001 8204181F59
TPOS24_QLT_SPP
Event suppression detected (TPOS24)
Table 4.9-35 PLC monitoring points (P1–P3 state signals in TPOSxx)
Signal Number
Signal Name
Description
513001 8304011D02
TPOS01_ST_P1
TPOS01 P1 On(0/1)
513001 8104011D03
TPOS01_ST_P2
TPOS01 P2 On(0/1)
513001 8504011D04
TPOS01_ST_P3
TPOS01 P3 On(0/1)
513001 8304021D02
TPOS02_ST_P1
TPOS02 P1 On(0/1)
513001 8104021D03
TPOS02_ST_P2
TPOS02 P2 On(0/1)
513001 8504021D04
TPOS02_ST_P3
TPOS02 P3 On(0/1)
513001 8104031D03
TPOS03_ST_P2
TPOS03 P2 On(0/1)
513001 8304031D02
TPOS03_ST_P1
TPOS03 P1 On(0/1)
513001 8504031D04
TPOS03_ST_P3
TPOS03 P3 On(0/1)
…
…
…
513001 8304181D02
TPOS24_ST_P1
TPOS24 P1 On(0/1)
513001 8104181D03
TPOS24_ST_P2
TPOS24 P2 On(0/1)
513001 8504181D04
TPOS24_ST_P3
TPOS24 P3 On(0/1)
(vi)
Setting names
Note: The “xx” of “TPOSxx” represents the TPOS function number. (e.g., if the TPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented from
“01” to “24”.)
Table 4.9-36 Setting for Binary input signals in TPOSxx
Setting Name
Description
Default
Setting item or value
TPOSxx-EN
Activate monitoring function of TPOS01-24
On
Off / On
TPOSxx-DEVTYPE
Equipment type selector.
switch
switch/EDS
TPOSxxP1-NOPSG
BI position for TPOS01-24
*none
BI signal
TPOSxxP2-NOPSG
BI position for TPOS01-24
*none
BI signal
TPOSxxP3-NOPSG
BI position for TPOS01-24
*none
BI signal
TPOSxx-SPPEN
Activate event suppression for TPOS01-24
On
Off / On
TPOS-NELD
Number of change to lock status.
10
0~99
TPOS-TELD
Time to locking state( sliding window )
10[sec]
1~99[sec]
TPOS-TELR
Time to unlocking state( sliding window )
10[sec]
1~99[sec]
Table 4.9-37 Settings for health check function in TPOSxx
Setting Name
Description
Default
Setting item or value
TPOSxx-P1SLBORD
Select BO signal (BO*-RB) from signal list
*none
BO readback signal
TPOSxx-P2SLBORD
Select BO signal (BO*-RB) from signal list
*none
BO readback signal
TPOSxx-P3SLBORD
Select BO signal (BO*-RB) from signal list
*none
BO readback signal
TPOSxx-P1EXBORD
Select BO signal (BO*-RB) from signal list
*none
BO readback signal
TPOSxx-P2EXBORD
Select BO signal (BO*-RB) from signal list
*none
BO readback signal
TPOSxx-P3EXBORD
Select BO signal (BO*-RB) from signal list
*none
BO readback signal
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......