6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 82 -
operate instantly. As shown in Figure 2.1-53, the reach of the zone1
(X)
is required to cover the
majority of the line length AB, whereas the zone1
(X)
should be independent on faults that occur
beyond the busbar B. Given the existence of the measuring errors in the VT and the CT,
approximate 80 to 90% of the line AB is required to set for the reach setting at the zone1
(X)
.
When the ZS/ZG function is used in the main relay, zero should be set for the both settings
[
TZ*S
] in order that tripping is executed instantly.
(ii)
Setting for adjacent lines (Zone2 serviced as a backup relay)
The reach setting in the zone2
(X)
is required to cover 100% of the line AB plus about 20% of the
adjacent line BC. To preserve the operation selectivity for the adjacent line BC (i.e., the
operation in the zone1
(Y)
), the user should set the reach of the zone2
(X)
not beyond the reach of
the zone1
(Y)
.
Note that setting TZ2
(X)
does not influence the CTI regarding the zone1
(Y)
. If delayed
tripping in the zone1
(X)
is preferred, the CTI between the zone2
(X)
and the zone1
(Y)
should be
taken into account. Note that setting TZ2
(X)
should be satisfied with Equations (2.1-39) and
𝑇𝑍2
(𝑋)
> 𝑇
𝑃
(𝑌)
+ 𝑇
𝐶𝐵
(𝑌)
+ 𝑇
𝑍𝑜𝑛𝑒2
(𝑋)
− 𝑇2
(𝑋)
(2.1-39)
𝑇𝑍2
(𝑋)
> 𝑇𝑍1
(𝑋)
(2.1-40)
where we have defined
Tp
(Y)
:
Maximum operating time in the main (primary) relay
(Y)
,
Tcb
(Y)
:
Opening time in the circuit breaker
(Y)
,
T2
(X)
:
Minimum operating time for the zone2
(X)
,
TZone2
(X)
: Reset time for the zone2
(X)
Figure 2.1-54 shows that the adjacent line BC is too short so that the coordination
between the zone1
(Y)
and the zone2
(X)
is
not realized straightforward. Hence, setting TZ2(X) is
required to be larger than setting TZ2(Y); consequently, the coordination between is achieved.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......