6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 504 -
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††
Note: To identify the output signals of the other SPOS logics, see Table 4.1-9.
Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_FSL_BO_CSF”.
1
Note: The signal “SPOS01_FSL_BO_CSF” is the same as the signal shown in Figure
4.1-4. If the “Local-OFF-Control” signal is not true, the SPOS01 function returns
to the “Wait for a command” stage.
(v)
Receiving “Selection command for ON” by PLC function
Figure 4.1-9 outlines the reception of the select command ‘On’ by the PLC function.
PLC logic programmed
by the user
Select command On by PLC
function
Signal output
Select
decision
Success
Failed
Selection logic
Selection logics
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from remote-end
Select command Off by the PLC
Select command On from remote-end
Select command Off from front panel
Select command On from front panel
Figure 4.1-9 Outline of select command ‘On’
Input signal required from the PLC function.
Figure 4.1-10 shows the select logic when a “Select command On (PLC-ON-Control)” signal is
generated by the PLC function. There are two input points for reception of this signal: The
former connection point (PLC#1) is used for the reception of the select-command requiring the
interlock check, the latter connection point (PLC#2) is used for the reception of the select-
command not requiring the interlock check. That is, for the SPOS01 function, when the “select
command ‘On’ (PLC-On-Control) signal generated in the user-programmed logic is applied, and
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......