6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 766 -
Signal acquisition logic in DPOS01
“DPOS01_3PH_STATE”
(512001 3103011001)
To select and operate
condition logics
[
DPOS01-DEVTYPE
]
1-Pol
e
Open
Faulty
Intermediate
Close
Event
Suppression
detector
BI signal selected by
setting [
DPOS01A-NOPSG
]
[
DPOS01-EN
]
On
&
BI signal selected by
setting [
DPOS01A-NCLSG
]
N/O contact
signal
N/C contact
signal
Single phase signals
&
&
1
≥
&
&
&
&
DPOS01
Signals from the
devices
Output
‡
“DPOS01_
F_QLT_SPP
”
(512001 8103011F5F)
BI circuit and DPOS01
Figure 4.8-41 Acquisition of single-phase signal at DPOS01
‡Note: In Figure 4.8-41 two signals can be issued “DPOS01_3PH_STATE” and
“DPOS01_F_QLT_SPP”, which are the same as the ones of the Figure 4.8-40.
Event suppression
If the status of a device “chatters” for a short time, the DPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPOS function;
hence, event suppression can be required to reduce additional burden created.
The DPOS function has an event suppression detector. The user should take into account
of the scheme switches [
DPOS-NELD
], [
DPOS-TELD
] and [
DPOS-TELR
]†. Set
On
for scheme
switch [
DPOS01-SPPEN
].
1 3 5 7
Signal
from device
On
On
On
On
On
On
On
On
2 4 6 8
On
On
On
[
DPOS-TELD
]
[
DPOS-TELR
]
[
DPOS-NELD
]
Suppressed
signal
A
C
D
E
B
Time.................
Figure 4.8-42 Iterative signals and signals suppressed
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......