6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 797 -
TPOS01 function (Function ID: 513001)
DEV01_P1_INTERLOCK
Operate command
without ILK
† condition
ILK
† condition (“P1”) passed
PLC in DIR operate
513001 800401EE31
510001 7001016D08
TPOS1-P1
Signals from user-PLC logic
Output
Selection logic in TPOS01
0.1s
0
t
0.6s
0
t
&
&
&
Select condition
‡
1
≥
P1-control command requiring
ILK† check
(PLC connection point #1)
DEV01_P1_COMMAND
513001 800401EE30
P1-control command not requiring
ILK† checking
(PLC connection point #2)
Operate command
with ILK
†
condition
For DIR operation
For DIR operation
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
Select
“Failed”
To BO connection
Select
“success”
To
“Wait for a command”
To
“Wait for a next
command
”
Figure 4.9-15 Select ‘P1-control’ by the PLC function in TPOS01
††
†Note: The ILK function provides the operation criteria for “P1-control”.
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
*Note: The TPOS01 function can run in either the “SBO mode” or the “DIR mode”. The
user can use signal called “ctlmodel” when communication is implemented using
IEC61850. To use this signal, the user must map for IEC61850 communication.
††
Note: To identify the input and output point of the other TPOS logics, see Table 4.9-8
for the inputs PLC#1 and PLC#2, Table 4.9-10 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.9-15, can issue a “Select success” signal at the output-point
“TPOS01_P1SL_BO_FLG”
1
.
1
Note: The “TPOS01_P1SL_BO_FLG” signal is the same as the signal shown in Figure
(viii)
Receiving “Select command P2-control” by PLC function
Figure 4.9-16 outlines the reception of the select command ‘P2-control’ by the PLC function.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......