6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1025 -
8.3.5
Trigger settings for PLC programming
If the PLC program instructs the operation of the disturbance recorder, the user should set the
[
Trigger ID1
] to [
Trigger ID4
]. That is, the program-output points should be set for the settings
[
Trigger ID1
] to [
Trigger ID4
]; then, set
On
for the [
Trigger SW1
] to [
Trigger SW4
], respectively.
8.3.6
Screen information
Figure 8.3-2 indicates the maximum number of the recording operations as the number is
changed depending on the time settings, which are shown in Table 8.3-1. Figure 8.3-3 shows
the operation time and the date for the disturbance recorder and the figure illustrates five
disturbance phenomena have been memorized in the IED.
Max. recording number for Disturbance phenomena
Disturbance Record
10:48
1/2
_Record List
>
Number of items
5/77
Clear Records
+
Operating counter
Figure 8.3-2 Running counter and Max number in the disturbance recorder
Disturbance Record
10:48
1/5
#
1 2012-07-25
10:48:21.223
#2 2012-07-21
01:15:55.018
#3 2012/07/21
13:11:29.621
#4 2012-07-02
23:32:09.015
#5 2012-06-20
09:37:48.915
Screen scroll down
○
a Disturbance record#1
○
b Disturbance record#2
○
d Disturbance record#4
○
e Disturbance record#5
○
c Disturbance record#3
Figure 8.3-3 Detail information in the disturbance recorder
The information in the disturbance recorder is managed in the COMTRADE format,
hence, the user can transfer the disturbance recording file to the PC using the engineering tool
‘GR-TIEMS’. Figure 8.3-4 shows the example of the GR-TIMES screen. For more information,
see
Chapter Engineering tool
.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......