6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 310 -
the ZS/ZG protections, see Chapter
Relay application: Distance protection, when
available.
3
Note: Output signals are provided for respective relays when the relays are available.
See
Appendix: Ordering whether the relays are supplied into the IED.
4
Note: AMF feature is used for the test. To generate the AMF signal, see chapter
User
interface: Test-submenu.
If a PLC signal is injected at the PLC connection point “VTF_BLOCK”, the operation of
the VTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_VTF; the VTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_VTF.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......