6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1230 -
specified COT regardless of cause of transmission.
(3)
If COT=9 is specified, the frame become the object of GI and is sent back when the
GI request frame is received. Time-tagged message is sent back in order of No.
instead of order of INF.
Table 11.4-8 shows the summary of (1), (2) and (3) above.
Table 11.4-8 COT setting pattern and COT supplemented frame
COT setting
pattern
COT supplemented frame when status changes
GI
1
9 11 12
Always “1”
No
Events don’t occur.
Yes
Always “11”
No
Always “12”
No
Always “1”
Yes
“11” (cause at local) or “1” (other causes)
No
“12” (cause at remote) or “1” (other causes)
No
Always “11”
Yes
Always “12”
Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes)
No
“11” (cause at local) or “1” (other causes)
Yes
“12” (cause at remote) or “1” (other causes)
Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes)
No
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes)
Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes)
Yes
Always “1” in spite of cause of event occurrence
No
Note: When being in the test mode, the COT=1(Spontaneous) is shifted to 7(Test
mode)
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......