6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 923 -
5.4.2
Binary input circuit
The binary input circuit has a threshold for the input voltage and the user can regulate the
threshold using scheme switches and settings. Additionally, the binary input circuit has a
function in response to chattering signals produced by bouncing contacts, a programmable logic
for retarding and inverting the signal, and the user can set the respective features with
settings. Table 5.4-3 shows the respective settings and ranges in the standard type. Table 5.4-4
shows the ones in the variable types.
Table 5.4-3 Setting items for binary input circuits in the standard type
Setting item
1
Range
Uni
ts
Contents
Default
Common
THRES_Lvl
Low/High
– Threshold level for input voltage
Low
CMP_NUM
4 to 9
– Number of times in the filter
4
BI1_CPL
Off/On
– Switch of programmable operation in BI1
Off
BI1
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
– Inversion operation of BI1 signal
Normal
BI2_CPL
Off/On
– Switch of programmable operation in BI2
Off
BI2
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
– Inversion operation of BI2 signal
Normal
BI3_CPL
Off/On
– Switch of programmable operation in BI3
Off
BI3
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
– Inversion operation of BI3 signal
Normal
…..
…..
…..
…..
…..
BI
n
_CPL
Off/On
– Switch of programmable operation in BI
n
Off
BI
n
2
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
– Inversion operation of BIn signal
Normal
1
Note: Setting items are provided in each slot; see Figure 5.4-4.
2
Note: BI
n_CPL and other settings are provided for all binary input circuits. For
example, the user can configure 18 CPLs in the BI1A module.
3
Note: Each setting item above is required to set at every IO_slots.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......