6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 813 -
[
TPOS01-LGP1EXOT
]. The “Operate-completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.9-26. The
user-programmed logic is connected internally to the signal “operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User-configurable condition”. That is, set the scheme switch [
TPOS01-
LGP1EXOT
] to
PLC
and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.9-27, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the received “Remote-P1-
Control” signal is true.
(ii)
Receiving “Operate command P2-control” from the remote-end
Figure 4.9-28 depicts the reception of the operate command ‘P2-control’ from the remote-end.
Signal reception in
IEC61850
P2 control from the remote-end
Do nothing
Operation
decision
Success
Failed
Operate logic
P1 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P2 control by the PLC function
Wait for a command
P2 control from the remote-end
P3 control by the PLC function
Select logics
Signal output
P1 control from the local-end
P2 control from the local-end
P1 control from the remote-end
P3 control from the remote-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Wait for a next command.
Figure 4.9-28 Outline of operate command ‘P2-control’
Input signal required mapping
Figure 4.9-19 illustrates the operate logic when an “Operate command P2 (Remote-P2-Control)”
signal is applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is used
for the reception of the “Operate command P2 (Remote-P2-Control)”.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......