6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 787 -
TPOS01 function (Function ID:
513001)
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
DEV01_CONTROL_REQ
Command
“P1-Control” from the remote
ILK
†
condition (“P1”) passed
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
In SBO operation
In DIR operate
Select
“Failed”
513001 7004016D08
TPOS1-P1
To BO connection
Input
Output
Selection logic in TPOS01
0.1s
0
t
0.6s
0
t
&
&
&
&
&
Select
“success”
“Automatic sequence control function (AQEQ)
§
” in progress
ASEQ_MULTI_SEL
Select condition
‡
1
≥
Select command
with ILK
†
condition
Operate command
with ILK
†
condition
Select command
without ILK
†
condition
Operate command
without ILK
†
condition
For SBO operation
For DIR operation
To
“Wait for a command”
For DIR operation
For SBO operation
To
“Wait for a next
command
”
Figure 4.9-3 Select P1-control from the remote-end in TPOS01
††
†Note: The software interlocking (ILK) function provides the operation criteria for “P1
control”. The ILK function is discussed separately; note that the operation criteria
is defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function being
in the operation. For more information of the ASEQ function, see Chapter
Control
and monitoring application: Automatic sequence control function.
*Note: The TPOS01 function can run in either the “SBO mode” or the “DIR mode”. The
user can use signal called “ctlmodel” when communication is implemented using
IEC61850. To use this signal, the user must map for IEC61850 communication.
††
Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,
Table 4.9-7, and Table 4.9-10.
Output signal to BO
The TPOS01 function can issue an signal “Select success” at the output point
“TPOS01_P1SL_BO_FLG”, when the TPOS01 function determines that the input signal
“Remote-P1-Control” received is true. If the TPOS01 function determines that the “Remote-
P1-Control” is not true, the TPOS01 function returns to the “Wait for a command” stage.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......