6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 871 -
4.10.4
Signal
Signal monitoring points in BI module at IO#1 slot
GENBI (Function ID: 580001)
Element ID
Name
Description
0010001001
SLOT1 GBI01_STATE
Status of binary input circuit BI1 at IO#1 slot
0010011001
SLOT1 GBI02_STATE
Status of binary input circuit BI2 at IO#1 slot
0010021001
SLOT1 GBI03_STATE
Status of binary input circuit BI3 at IO#1 slot
….
….
….
00101F1001
SLOT1 GBI32_STATE
Status of binary input circuit BI32 at IO#1 slot
Mapping points in BI module at IO#1 slot
GENBI (Function ID: 580001)
Element ID
Name
Description
3110001005
SLOT1 GBI01_QUALITY
SLOT1 GBI01 quality
3110011005
SLOT1 GBI02_QUALITY
SLOT1 GBI02 quality
3110021005
SLOT1 GBI03_QUALITY
SLOT1 GBI03 quality
…
…
…
31101F1005
SLOT1 GBI32_QUALITY
SLOT1 GBI32 quality
0010001001
SLOT1 GBI01_STATE
SLOT1 GBI01 state
0010011001
SLOT1 GBI02_STATE
SLOT1 GBI02 state
0010021001
SLOT1 GBI03_STATE
SLOT1 GBI03 state
…
…
….
00101F1001
SLOT1 GBI32_STATE
SLOT1 GBI32 state
9010001006
SLOT1 GBI01_TIMESTAM
SLOT1 GBI01 timestamp
9010011006
SLOT1 GBI02_TIMESTAM
SLOT1 GBI02 timestamp
9010021006
SLOT1 GBI03_TIMESTAM
SLOT1 GBI03 timestamp
….
….
….
90101F1006
SLOT1 GBI32_TIMESTAM
SLOT1 GBI32 timestamp
Note: In the table above, the user will only find Element IDs and their names for the 1
st
slot, but a 2
nd
and other slots are also provided in the GENBI function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every circuit;
hence, the user can find the same ones for all of the other circuits. For
example, when the user wishes to find the “SLOT2 GBI02_STATE” point
for the 2
nd
circuit, use the description of SLOT1 GBI01_STATE in place of
“SLOT2 GBI02_STATE”. The user can obtain the ID value of “SLOT2
GBI02_STATE” by using the following steps:
Step 1
Find the element ID for SLOT1 GBI01_STATE (i.e.,
“0010001001”)
Step 2
Identify the number at the fifth and sixth digits from the
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......