6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1248 -
RS485 communication
When the IED has an RS485 module for the communication, the user can select and set its
transmission and error check parity codes. Figure 11.6-1 shows the setting screen when the
RS485 module (#1) operates.
RS485
10:48
1/2
RS485_1_BRATE_SW +
19.2kbps
RS485_1_BRATE_SW +
NONE
Figure 11.6-1 RS485 setting menu (on IED screen)
Setting of RS485 (Function ID: 232201)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Module
#1
RS485_1_BRATE_SW
9.6 / 19.2 / 38.4 /57.6 / 115.2
kbps
Transmission speed
19.2
RS485_1_PAR_SW
NONE / ODD /EVEN
–
Parity check code
NONE
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......