6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1168 -
Table 11.3-4 Data structures in the GOOSE
Logical Device
Category
“System”
Other Logical device (e.g., “Relay”)
Data Model
System
DataSet “GOOSEDS”
GGIO1 Ind1..16
LLN0
GoCB
The DataSet “GOOSEDS” is fixed
LPHD1
GGIO
Relay
LLN0
GoCB
LPHD1
PTRC
….
Data set
Fixed (Not configurable)
Configurable
Performance GOOSE data sent communication time
is < 3msec
GOOSE data sent, communication
time is around 10msec
(iii)
System
The data model in the LN named “System” is not allowed to modify (that is, a data model is
fixed; other LN data models are configurable to meet the system requirement). Mapping
signals to the GGIO1 is required when the GOOSE should send data faster.
(iv)
Control mode using GOOSE
In the IED, signals generated on the binary output circuit (BO) can be controlled by the SAS,
if the user makes the link between a reviving control message and a control function block that
changes the state of the output element. Four control modes are provided:
DOes:
Direct control with normal security (direct-operate)
SBOns:
SBO control with normal security (operate-once or operate-many)
DOes:
Direct control with enhanced security (direct-operate)
SBOes:
SBO control with enhanced security (operate-once or operate-many)
(v)
Time synchronization using IEC 61850 protocol / SNTP
SNTP (Simple network time protocol) is used to synchronize clocks of all IEDs in SAS. Time
synchronization is required to maintain common time across all IEDs in the network. This
makes it easier to analyze the Time stamped event data generated by the IEDs in chronological
order. In the system, IEDs are synchronized with the device having precision time source (for
example, GPS).
(vi)
File transfer (COMTRADE)
To send data of the disturbance records, file transfer service is used, which is the operated in
COMTRADE format.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......