6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 681 -
(ii)
Split-synchronism-check element (SyncRy1-
θ
=0, SyncRy1-
θ
less)
With regard to the connection of asynchronous networks, it is necessary to use the technique
of split synchronism to avoid the occurrence of cycle-slip on the system. The technique consists
of three parts: (1) calculation of the synchronization point (SyncRy1-θ=0), (2) check for slip
cycle (SyncRy1-θless), and (3) advance time for issuing the closure command.
Calculation of synchronization point
Issuing a closure command for the CB is appropriate when the variance of Vr and Vi is
small. Hence, the timing of when it should be issued is calculated in the SyncRy1-θ=0 element
so that the prediction of coincident timing between the running, (Vr) and the incoming, (Vi)
voltages can be introduced. Figure 4.6-6(c) shows the coincident point (zero point).
Check for slip cycle
Checking the decrease in Δθ is a suitable means for controlling the issue of a closure command
to a CB at the requisite timing. The SyncRy1-θless element calculates the for reducing Δθ; it
assists in the computation of the SyncRy1-θ=0 element.
Advance time
The user shall consider the actual device operation time. For an asynchronous network, the
issue of the CB closure command should be initiated such that it is coordinated with the actual
closing. Figure 4.6-6 shows the advancing time; it is introduced with setting [
SyncRy1-TCB
],
closing time (Tcb) and compensation time:
Setting[
SyncRy1-TCB
] = α + T
CB
+ 𝛽
(4.6-14)
where,
α:
Operation time of the element
β:
Compensation (i.e., tolerance) time
Tcb:
Closing time of CB
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......