6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 97 -
ZG (Function ID
:
431001
)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z1G-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z1G-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
TZ1G
0.00 - 100.00
s Z1G operation delay time
0.00
Z1G-CovCoeff
1.5 - 10.0
- Covered characteristic size coefficient
1.5
Output
Z1G-EFL
Off / On
-
EFL operation condition used or not for Z1G
operation
On
Z1G-MPFBlk
Non / Block
- Z1G operation block or not in multi phase fault
Block
Z1G-PSBBlk
Non / Block
- Z1G operation block or not by PSB detection
Block
Z1G-LEBlk
Non / Block
- Load encroachment enable
Non
Z1G-LPBlk
Non / Block
- Z1G leading phase operation block
Non
Z1G-TPMD
1P / 3P
-
Z1G trip mode, phase segregated trip or 3-
phase trip
1P
Z1G-ARCBlk
Non / Block
- Autoreclose execution block by Z1G-trip
Non
Z1G-OCFS-EN
Off / On
- Fail-safe OC for Z1G-trip
Off
OCF1G
0.02 - 5.00
0.10 -
25.00
A Fail-safe OC operation level for Z1G-trip
0.20
1.00
Z1G-SOTF
Off / On
- SOTF using Z1G
Off
Z2G
Z2G-Dir
Forward / Reverse /
NonDir
- Z2G direction to protect
Forward
Mho
Z2G-Mho.Angle
30 - 90
deg Z2G mho characteristic angle (for Mho)
85
Z2G-
Mho.Reach
0.10 -
500.00
0.01 -
100.00
- Z2G mho reach (for Mho)
20.00
4.00
Z2G-MhoX.EN
Off / On
- Z2G reactance reach use or not (for Mho)
Off
Z2G-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z2G reactance reach
20.00
4.00
Z2G-MhoR.EN
Off / On
- Z2G resistive reach use or not (for Mho)
Off
Z2G-R.Angle
30 - 90
deg Z2G resistive reach characteristic angle
75
Z2G-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z2G resistive reach
25.50
5.10
Z2G-
MhoDX.EN
Off / On
-
Z2G directional-X characteristic use or not (for
Mho)
Off
Z2G-DX.Angle
0 - 60
deg Z2G directional-X characteristic angle
30
Quad
Z2G-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z2G reactance reach
20.00
4.00
Z2G-R.Angle
30 - 90
deg Z2G resistive reach characteristic angle
75
Z2G-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z2G resistive reach
25.50
5.10
Z2G-DX.Angle
0 - 60
deg Z2G directional-X characteristic angle
30
Z2G-DR.Angle
0 - 60
deg
Z2G directional-R characteristic angle (for
Quad)
5
I0K
Z2G-Krs
0 - 1000
% Zero phase current factor, Self line R0/R1
100
Z2G-Kxs
0 - 1000
% Zero phase current factor, Self line X0/X1
100
Z2G-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z2G-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
TZ2G
0.00 - 100.00
s Z2G operation delay time
0.30
Output
Z2G-EFL
Off / On
-
EFL operation condition used or not for Z2G
operation
On
Z2G-MPFBlk
Non / Block
- Z2G operation block or not in multi phase fault
Non
Z2G-PSBBlk
Non / Block
- Z2G operation block or not by PSB detection
Non
Z2G-LEBlk
Non / Block
- Load encroachment enable
Non
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......