6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 579 -
DPSY01 function (Function ID: 511001)
Assign to BOs
Operate Cmd.
with ILK
† condition
[
DPSY01-PLSM
]
*
Var
Fix
S
R
Operate Failed
0.1
– 50.0 s
[
DPSY01-RST
]
[
DPSY01-CPW
]
Operation Cmd.
without ILK
† condition
Operate condition
‡
[
DPSY01-LGCTRCON
]
Fixedlogic
Fixedlogic
[
DPSY01-LGCFEXOT
]
ILK
†
condition (“Open”) passed
DPSY01-Open
ASEQ function
§
” is in progress
ASEQ_MULTI_SEL
DPSY01IN_TMP_34
511001 800201EE56
User configurable condition
(PLC#3 connection point)
“DPSY01_FEC_OK_CSF”
(511001 8002011E7E)
“DPSY01_FEC_OK_CSF”
(511001 8002011E7E)
&
&
1
≥
&
1
≥
1
≥
&
&
&
“DPSY01_FEX_BO”
§§
(511001 8102011DD0)
“DPSY01_EX_FFL”
††
(511001 8602011E91)
Input
Output
Operate logic in DPSY01
PLC#1
To BO connection
To
“Wait for a command”
“DPSY01_FEC_OK_CS”
(511001 8002011E7E)
&
Detection of state-change in a device
&
PLC#2
DPSY01IN_TMP_44
511001 820201EE5E
User configurable condition
(PLC#2 connection point)
1
≥
&
“DPSY01_EX_CMP”
(511001 8002011E93)
Operate Completed
Command
“PLC-Open-Control” with ILK†
(PLC#4 connection point)
DEV01_OP_INTERLOCK
511001 800201EE31
Command
“PLC-Open-Control” without ILK†
(PLC#5 connection point)
DEV01_OP_COMMAND
511001 800201EE30
1.0s- 100.0s
0
t
Figure 4.2-30 Open operation logic by PLC in DPSY01
††
†Note: The ILK function can provide the criteria for operation for control of the “Open”
operation.
‡Note: An “operate condition” signal is generated in the operate-condition logic (see
Fixlogic
is set for scheme switch [
DPSY01-LGCTRCON
]. If an
alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operated-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 1.10-30 using
connection point #3 “User-configurable condition”. That is, set the scheme switch
[
DPSY01-LGCTRCON
] to
PLC
and use “DPSY01IN_TMP_34”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when
Fixlogic
is set for the scheme
switch [
DPSY01-LGCFEXOT
]. If the signal to be issued from the programmed
logic by the user in place of Figure 4.2-20 logic, connect the signal “Operate
completed” generated in the programmed logic to the connection point #2 “User
configurable condition”. That is, the set the scheme switch [
DPSY01-LGCFEXOT
]
to
PLC
and use “DPSY01IN_TMP_44”.
*Note: The user can set the type of the output signal. When
Var
is set for scheme switch
[
DPSY01-PLSM
], the output period of the signal is defined by the setting applied
to [
DPSY01-CPW
]. When
Fix
is set, the signal ceases when the 43-switch is
changed.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......