6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 425 -
2.28.1
Scheme logic
State transition diagram and scheme logic are shown in Figure 2.28-1 and Figure 2.28-2. It
should be noted that the scheme logic requires two binary inputs: circuit breaker (CB) OPEN
and circuit breaker (CB) CLOSED.
Under the normal operation, where the CB is closed, the CLP stays in STATE 0, and the
OC operates with a normal setting group.
When the CB opens, the scheme moves into STATE_1, then Cold-load-enable-timer
(TCLP) runs. If the CB closes again while the TCLP is running, the scheme will re-enter into
STATE_0. If the TCLP expires and the load is in cold, the scheme moves into STATE_2. When
the CB closes again, the scheme moves into STATE_3.
Cold-road-reset-timer (TCLP) runs at STATE_3. If the CB re-opens while the TCLP is
running, the scheme returns into STATE_2. If the TCLP is time out, the scheme moves into
STATE_0, where the load is considered as warm, and the setting of normal operation is applied
again.
At STATE_2 and STATE_3, the setting group of the CLP is applied. The operation of the
CLP is forbidden by placing set of
OFF
for the scheme switch [
CLP-EN
].
Accelerated reset of the CLP is also possible. As being at STATE_3, poly-phase currents
are monitored by the function of inrush current detection (ICD). If poly-phase currents plunge
below the setting of ICD threshold, and when the duration of the plunge is longer than setting
[
TCLP_DO
], then the scheme automatically reverts into STATE_0. By placing set of
ON
for
scheme switch [
CLP-DOEN
], it is possible for the reset function to accelerate.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......