6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
89
ZS (Function ID
:
430001
)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z1S-EN
Off / On
- Z1S protection enable
Off
Z2S-EN
Off / On
- Z2S protection enable
Off
Z3S-EN
Off / On
- Z3S protection enable
Off
Z4S-EN
Off / On
- Z4S protection enable
Off
Z5S-EN
Off / On
- Z5S protection enable
Off
Z1XS-EN
Off / On
- Z1XS protection enable
Off
Comm.
ZS-Chara
Quad / Mho
- Selection of ZS relay character
Quad
ZSF-
X.GrAngle1
0 - 45
deg
ZS-forward gradient characteristic angle (for
Quad and Mho-X)
0
ZSF-
X.GrAngle2
45 - 90
deg
ZS-forward gradient characteristic angle (for
Quad and Mho-X)
75
PSBS
PSBSZ
2.50 -
75.00
0.50 -
15.00
- Power swing block detection
10.00
2.00
TPSBS
0.020 - 0.100
s Power swing block detection timer
0.040
PSBSFR
Off / On
- Power swing block reset enable
On
TPSBSFR
0.00 - 10.00
s Power swing block reset timer
1.00
PSBSRS
Off / On
-
Power swing block reset enable when a fault
has occurred
Off
LES
LESR
0.10 -
500.00
0.01 -
100.00
- Minimum load resistance on the right
25.50
5.10
LESR-Angle
5 - 75
deg Maximum load angle on the right
10
LESL
0.10 -
500.00
0.01 -
100.00
- Minimum load resistance on the left
25.50
5.10
LESL-Angle
5 - 75
deg Maximum load angle on the left
10
Z1S
Z1S-Dir
Forward / Reverse /
NonDir
- Z1S directional characteristic
Forward
Mho
Z1S-Mho.Angle
30 - 90
deg Z1S mho characteristic angle (for Mho)
85
Z1S-Mho.Reach
0.10 -
500.00
0.01 -
100.00
- Z1S mho reach (for Mho)
8.00
1.60
Z1S-MhoX.EN
Off / On
- Z1S reactance reach use or not (for Mho)
Off
Z1S-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z1S reactance reach
8.00
1.60
Z1S-
X.GrAngleEN
Off / On-Set / On-
Adapt
- ZS gradient characteristic
Off
Z1S-MhoR.EN
Off / On
- Z1S resistive reach use or not (for Mho)
Off
Z1S-R.Angle
30 - 90
deg Z1S resistive reach characteristic angle
75
Z1S-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z1S resistive reach
25.50
5.10
Z1S-
MhoDX.EN
Off / On
-
Z1S directional-X characteristic use or not (for
Mho)
Off
Z1S-DX.Angle
0 - 60
deg Z1S directional-X characteristic angle
30
Quad
Z1S-X.Reach
0.10 -
500.00
0.01 -
100.00
- Z1S reactance reach
8.00
1.60
Z1S-
X.GrAngleEN
Off / On-Set / On-
Adapt
- ZS gradient characteristic
Off
Z1S-R.Angle
30 - 90
deg Z1S resistive reach characteristic angle
75
Z1S-R.Reach
0.10 -
500.00
0.01 -
100.00
- Z1S resistive reach
25.50
5.10
Z1S-DX.Angle
0 - 60
deg Z1S directional-X characteristic angle
30
Z1S-DR.Angle
0 - 60
deg
Z1S directional-R characteristic angle (for
Quad)
5
TZ1S
0.00 - 100.00
s Z1S operation delay time
0.00
Z1S-CovCoeff
1.5 - 10.0
- Covered characteristic size coefficient
1.5
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......