6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1070 -
(ii)
Error LED and LCD error message
The IED has LEDs and LCD screen† so that the automatic supervision function issues a result
for the LEDs and the LCD screen. When the IED is linked with the SAS, it is possible to
transfer the result for the LED and LCD screen using the communication system. Table 10.1-2
shows that which indicators are used for result generation in the function.
Table 10.1-2 Displays on LEDs, LCD, and SAS
Levels
“In service” LED
“Error” LED
Error message on LCD
0: No error
On
Off
(Not displayed)
1: Serious
Off
On
Displayed
2: Serious (Comm.)‡
On
On
Displayed
3: Minor
On (Off§)
On
Displayed
4: Alarm
On
Off
Displayed
5: Warning
On
Off
Displayed
†Note: For more information, see
Chapter User interface: Outline and Diagnostics.
‡Note: It depends on the degree of the communication failure.
§Note: If the “In service” has to be turned off while a minor error (level:3) is occurring, set
On
for the setting [
ErrorLED_cond
].
The user can see a current error information in Monitoring sub-menu† on the LCD screen†
(see Figure 10.1-1); Table 10.1-3 shows the six detail information, which the user can examine
carefully using the hexadecimal number. When two or more errors occur at the same time, an
error code is given by the summation of the error codes. That is, when X and Y errors (e.g., X-
error-code ‘00000002’ and Y-error-code ‘00000004’) occur, the sum value ‘00000006’ is screened.
CP1M(ROM/RAM) error
10:48
[Serious error]
1/1
[00000011] [01234567]
[01234567] [01234567]
[01234567] [00000000]
“
Top left
”
“
Top right
”
“
Middle left
”
“
Middle right
”
“
Bottom left
”
“
Bottom right
”
[
] [
]
[
] [
]
[
] [
]
7 6 5 4 3 2 1 0
D e t a i l e d i n f o r m a t i o n i n H e x a d e c i m a l d u m p
C u r r e n t l o c a l t i m e ( N o t E r r o r o c c u r r i n g t i m e )
C u r r e n t e r r o r i n d i c a t e d b y S u p e r v i s i o n
E r r o r d e g r e e ( l e v e l ) d i s p l a y e d
Figure 10.1-1 Example error codes and detailed information on Diagnostics sub-menu
†Note: See Chapter
User interface: Monitoring sub-menu: Diagnostics. It will not be
updated automatically. If new information is required, refresh LED screen again.
Table 10.1-3 Detailed information in Hexadecimal in the ROM and the RAM error (example)
Display
area
Meaning of the detailed information
Left column
Right column
Top row
00000001: ROM read error
00000002: ROM RAM mismatch ROM address
Middle row
RAM address
ROM value
Bottom row
RAM value
(No information displayed)
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......