6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 359 -
ARC1 and ARC2 functions being generating ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’
signals. The switch [
FT-3P FAULT
] requires signals of the external relay; PLC connection
points ‘RYOP-A, RYOP-B, and RYOP-C’ are used to get the signals.
Note that the ‘CB1_94TT’ and ‘CB2_94TT’ signals are generated when ‘ARC BLOCK’
signals are injected, provided ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’ signals is being
generated.
If, with regard to the tripped poles of CBs, there is not consistency between the CB#1 and
the CB#2, the ARC function can generate the ‘CB1_94TT’ and ‘CB2_94TT’ signals when an
external device is able to detect the consistency; use PLC connection points ‘F.CB1_94TT’ and
‘F.CB2_94TT’ for the operation of the inconsistency.
The Start logic can receive a stop signal not to operate the ARC function; use PLC
connection point ‘ARC NO ACT’.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......