6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 793 -
Keying
“Select
command
”
P2control from the local-end
Signal output
Select
decision
Success
Failed
Selection logic
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Select stage
Cancel logic
Wait for a command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
P1 control from the remote-end
Figure 4.9-10 Outline of select command for ‘P2-control’
Input signal generated at the local-end
Figure 4.9-11 shows the select logic when a “Select command P2 (Local-P2-Control)” signal is
applied to the TPOS01 function. The signal is provided when the user presses a “Local-P2-
control” key on the IED front panel; the user is not required to take account of mapping.
Input
Output
Selection logic in TPOS01
Command
“Local-P2-Control”
TPOS1-P2
ILK
†
condition (“P2”) passed
ILK
†
bypassing
1≥
ICB_STATE
[
TPOS01-CTRAHMI
]
SBO
TPOS01 function (Function ID:
513001)
SBO
DIR
&
&
1≥
&
0.1s
0
t
0.6s
0
t
Either
“SBO mode” or “DIR mode”
(e.g.,
“ctlmodel” in IEC61850
*
)
“Automatic sequence control function (AQEQ)
§
” in progress
ASEQ_MULTI_SEL
Select condition
‡
“TPOS01_P2SL_BO_FLG”
(513001
_
8A04011DC6)
Select
“Failed”
To BO connection
Select
“success”
To
“Wait for a command”
Select command
with ILK
†
condition
Operate command
with ILK
†
condition
For SBO operation
For DIR operation
Figure 4.9-11 Select P2-control on the front panel in TPOS01
††
†Note: The ILK function provides the operation criteria for “P2-control”.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......