6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 515 -
(iii)
Cancel condition logic
Figure 4.1-18 shows the cancel condition logic. As the criteria, “unmatched condition detected”
is connected normally for the cancel logic, set
Fixlogic
for the scheme switch
[
SPOS01_LGCNFFC
].
SPOS01 function (Function ID: 510001)
User configurable condition (PLC connection point)
Fixedlogic
[
SPOS01-LGSLFFCT
]
To cancel logic in
SPOS01
Unmatched condition detected *1
SPOS01IN_TMP_46
510001 800101EE69
&
&
1
≥
Figure 4.1-18 Logic “Cancel condition” in SPOS01
1
Note: The Criteria “unmatched conditions” are determined when the “Test-bit status” in
the cancel command is not identical to the “IED test status”, like in Figure 4.1-13.
2
Note: With the exception of the above ‘cancel’ condition logic, there is an operate-
condition logic within the SPOS01 function; the operate-condition logic will always
checks conditions. That is, the user is required to set either the “operate-
condition” or the “cancel-condition” logic.
If the original logic does not meet with the requirements of the user, it can be replaced
with another logic using the connection point “User Configurable condition”:
1.
Connect the user-customized logic with the “SPOS01IN_TMP_46”.
2.
Set scheme switch [
SPOS01-LGCNFFCT
] to
PLC
.
(iv)
Signal name and number
Note: The user should note the following descriptions shown in the column “M/O” in
each table:
“O” indicates that the signal is provided for optional use.
“M” indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure for the default
settings.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.1-11 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number
Signal Name
Description
M/O
510001 800101EE69
SPOS01IN_TMP_46
SPOS01 user configurable cancel condition
O
510001 800102EE69
SPOS02IN_TMP_46
SPOS02 user configurable cancel condition
O
510001 800103EE69
SPOS03IN_TMP_46
SPOS03 user configurable cancel condition
O
…
…
…
510001 800114EE69
SPOS20IN_TMP_46
SPOS20 user configurable cancel condition
O
Table 4.1-12 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number
Signal Name
Description
510001 8601011E95
SPOS01_CC_SS
Cancel succeed in SPOS01
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......