6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 771 -
Setting for the contact health check (normal setting, example #1)
Figure 4.8-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.8-29, to
demonstrate that the settings are physically matched with the BO contacts.
Table 4.8-29 Setting example for contact health check
Example #1
Contact health check settings for example #1
“DPOS01_OSL_BO_FLG” is connected to “BO1” at IO#1
200B01 8002001113(BO1-RB) set for [
DPOS01-OSLORD
]
OK
“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1
200B01 8102011113 (BO2-RB) set for [
DPOS01-FSLBORD
] OK
“DPOS01_OEX_BO_CSF” is connected to “BO3” at IO#1
200B01 8202021113(BO3-RB) set for [
DPOS01-OEXBORD
] OK
“DPOS01_FEX_BO_CSF” is connected to “BO4” atIO#1
200B01 8302031113(BO4-RB) set for [
DPOS01-FEXBORD
]
OK
Plus (+)
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
SW1 driven with
BO1 at IO#1
BO1
Drivers
Select command On
“BO1-RB”
(200B01
_
8002001113)
BO3
“DPOS01_OEX_BO”
(512001 8203011DD3)
“BO4-RB”
(200B01
_
8302031113)
BO4
“DPOS01_FEX_BO”
(512001 8103011DD0)
“BO3-RB”
(200B01
_
8202021113)
SW2 driven with
BO2 at IO#1
SW4 driven with
BO4 at IO#1
Remote/Local-end
SW 3
SW 1
Minus (
−)
BIO module
43SW
On
command
BO2
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4)
“BO2-RB”
(200B01
_
8102011113)
SW 2
SW 4
SW3 driven with
BO3 at IO#1
Select command Off
Operate command On
Operate command Off
Off
command
Figure 4.8-49 Contact health check setting and 43SW scheme for example #1
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......