6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 985 -
consists of a binary input circuit (BI1), a number generation function (‘Binary selection’
provided in basic functions of the PLC editor), and the signal reception point. That is, when
the B1 switch is closed, a signal enters the BI1 circuit and is carried to the Binary selection;
accordingly the Binary selection, which is programmed to generate a group number ‘2’ in UNIT
when signal ‘1’ is injected in BOOL(BIT), can generates and inject the group number ‘2’ at the
‘PLC_Group_ENUM’. Consequently, the Setting function (201400) starts change the group
from number ‘1’ to ‘2’. Note that changing is only performed during the BI1 is closed in the
example logic; hence, the setting number goes back to ‘1’ when the BI1 is open.
IO_SLOT1 (200B01)
Binary input circuits BI1 and BI2
at IO#1 (IO_SLOT1)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
1
DIN_BOOL
DO
ST
2
SEL
G
Unit#16#1
IN0
IN1
Unit#16#2
3
DOUT_UNIT
FID
DTYPE
DID
ST
DI
Unit#16#201400
Unit#16#31
Unit#16#4000E1A0
PLC_Group_ENUM
201400 314000E1A0
PLC basic-function
(SEL)
BI1
‘1’ in BOOL
Entering → Leaving
Binary selection
Operation of
changing
‘2’ in UNIT
‘0’ in BOOL
‘1’ in UNIT
A group number enters
to “Setting function (FunctionID: 201400)”
(+) (–)
BI1
GR200 IED
BI2
8101011110
8001001110
BI2
FID
DTYPE
DID
1
DIN_BOOL
DO
ST
FID
DTYPE
DID
2
RS
Q1
SET
RESET1
PLC basic-function
(Flip-Flop)
Figure 5.8-2 Example for changing a group setting
4
1
Note: Function block for the binary input circuit (Binary input FB) is provided in User
library of PLC editor. See the Chapter
PLC editing in Basic manual
“Programmable Logic Controller and PLC editor” attached the PLC software.
2
Note: The SEL and RS functions are the basic functions. In the logic, when signal ‘1’
enters the SEL function, value ‘2’ is generated. For more information, see the help
menu on the PLC editor.
3
Note: For your reference, changing to group3 is performed when value ‘3’ enters. In
other words, values ‘1’ to ‘8’ correspond to ‘group1’ to ‘group8’, respectively.
4
Note: This example is designed to change ‘group1’ to ‘group2’ or ‘group2’ to ‘group1’.
Figure 5.8-3 exemplifies that selecting a group among eight groups is required by the
usage of three BI circuits (i.e., Group 1→Group2, Group3,… Group8).
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......